TEMPERATURE RATING | |
---|---|
Maximum maintain or continuous exposure temperature(power on) |
65℃ |
Maximum intermittent exposure temperature, 1000 hours (power on or off) |
85℃ |
Minimum installation temperature |
-40℃ |
3 BTV-CR/CT |
||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||
temperature |
120V |
240V |
||||||
at start-up |
15A |
20A |
30A |
40A |
15A |
20A |
30A |
40A |
10℃ |
101 |
101 |
101 |
101 |
201 |
201 |
201 |
201 |
-18℃ |
61 |
81 |
101 |
101 |
120 |
162 |
201 |
201 |
-29℃ |
53 |
72 |
101 |
101 |
107 |
142 |
201 |
201 |
-40℃ |
47 |
62 |
94 |
101 |
94 |
125 |
189 |
201 |
5 BTV-CR/CT |
||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||
temperature |
120V |
240V |
||||||
at start-up |
15A |
20A |
30A |
40A |
15A |
20A |
30A |
40A |
10℃ |
70 |
82 |
82 |
82 |
140 |
165 |
165 |
165 |
-18℃ |
43 |
58 |
82 |
82 |
87 |
116 |
165 |
165 |
-29℃ |
38 |
50 |
76 |
82 |
76 |
101 |
152 |
165 |
-40℃ |
34 |
44 |
67 |
82 |
67 |
90 |
134 |
165 |
8 BTV-CR/CT |
||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||
temperature |
120V |
240V |
||||||
at start-up |
15A |
20A |
30A |
40A |
15A |
20A |
30A |
40A |
10℃ |
46 |
61 |
64 |
64 |
91 |
122 |
128 |
128 |
-18℃ |
30 |
40 |
61 |
64 |
61 |
81 |
122 |
128 |
-29℃ |
26 |
35 |
53 |
64 |
53 |
72 |
107 |
128 |
-40℃ |
24 |
32 |
47 |
64 |
47 |
64 |
96 |
128 |
10 BTV-CR/CT |
||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||
temperature |
120V |
240V |
||||||
at start-up |
15A |
20A |
30A |
40A |
15A |
20A |
30A |
40A |
10℃ |
37 |
49 |
55 |
55 |
73 |
96 |
110 |
110 |
-18℃ |
24 |
34 |
49 |
55 |
49 |
66 |
99 |
110 |
-29℃ |
21 |
29 |
43 |
55 |
44 |
58 |
87 |
110 |
-40℃ |
20 |
26 |
38 |
52 |
38 |
52 |
78 |
104 |
TEMPERATURE RATING | |
Maximum maintain or continuous exposure temperature(power on) |
121℃ |
Maximum intermittent exposure temperature, 1000 hours (power on or off) |
215℃ |
Minimum installation temperature |
-40℃ |
5 HXTV |
||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||||
temperature |
120V |
240V |
||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
55 |
73 |
110 |
117 |
117 |
110 |
146 |
219 |
233 |
233 |
-18℃ |
49 |
64 |
98 |
117 |
117 |
96 |
128 |
191 |
233 |
233 |
-29℃ |
46 |
61 |
93 |
117 |
117 |
90 |
120 |
181 |
233 |
233 |
-40℃ |
44 |
59 |
88 |
117 |
117 |
87 |
116 |
174 |
232 |
233 |
10 HXTV |
||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||||
temperature |
120V |
240V |
||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
34 |
44 |
67 |
82 |
82 |
67 |
90 |
134 |
165 |
165 |
-18℃ |
29 |
40 |
59 |
79 |
82 |
59 |
79 |
117 |
157 |
165 |
-29℃ |
29 |
38 |
58 |
76 |
82 |
56 |
75 |
113 |
151 |
165 |
-40℃ |
27 |
37 |
55 |
73 |
82 |
53 |
72 |
108 |
143 |
165 |
15 HXTV |
||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||||
temperature |
120V |
240V |
||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
23 |
30 |
46 |
61 |
67 |
46 |
61 |
91 |
122 |
136 |
-18℃ |
20 |
27 |
41 |
55 |
67 |
40 |
53 |
81 |
108 |
134 |
-29℃ |
20 |
26 |
40 |
52 |
66 |
38 |
50 |
76 |
102 |
128 |
-40℃ |
18 |
24 |
38 |
50 |
62 |
37 |
49 |
73 |
98 |
123 |
20 HXTV |
||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
|||||||||
temperature |
120V |
240V |
||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
18 |
24 |
37 |
49 |
58 |
35 |
46 |
70 |
93 |
116 |
-18℃ |
15 |
21 |
32 |
43 |
55 |
30 |
41 |
62 |
84 |
105 |
-29℃ |
15 |
20 |
30 |
41 |
52 |
30 |
40 |
61 |
81 |
101 |
-40℃ |
15 |
20 |
30 |
40 |
50 |
29 |
38 |
58 |
78 |
98 |
TEMPERATURE RATING | |
Maximum exposure temperature (power off) | 260℃ |
Minimum installation temperature |
-40℃ |
Maximum Continuous maintain (power on) temperature table |
||||||
CABLE |
120V |
208V |
230V |
240V |
277V |
480V |
5VPL1-CT |
230℃ |
|||||
10VPL1-CT |
205℃ |
|||||
15VPL1-CT |
170℃ |
|||||
20VPL1-CT |
150℃ |
|||||
5VPL2-CT |
235℃ |
230℃ |
230℃ |
225℃ |
||
10VPL2-CT |
220℃ |
210℃ |
205℃ |
200℃ |
||
15VPL2-CT |
210℃ |
190℃ |
170℃ |
115℃ |
||
20VPL2-CT |
150℃ |
150℃ |
150℃ |
|||
5VPL4-CT |
230℃ |
|||||
10VPL4-CT |
205℃ |
|||||
15VPL4-CT |
170℃ |
|||||
20VPL4-CT |
150℃ |
VPL 5W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE |
|||||||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
||||||||||||||
temperature |
120V |
240V |
480V |
||||||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
260 |
79 |
107 |
113 |
113 |
113 |
160 |
209 |
226 |
226 |
226 |
320 |
418 |
451 |
451 |
-18℃ |
240 |
73 |
99 |
113 |
113 |
113 |
148 |
197 |
226 |
226 |
226 |
296 |
393 |
451 |
451 |
-29℃ |
235 |
72 |
96 |
113 |
113 |
113 |
143 |
191 |
226 |
226 |
226 |
287 |
381 |
451 |
451 |
-40℃ |
225 |
69 |
93 |
113 |
113 |
113 |
139 |
186 |
226 |
226 |
226 |
277 |
372 |
451 |
451 |
VPL 10W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE |
|||||||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
||||||||||||||
temperature |
120V |
240V |
480V |
||||||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
40 |
53 |
79 |
79 |
79 |
79 |
107 |
160 |
160 |
160 |
158 |
213 |
320 |
320 |
320 |
-18℃ |
37 |
50 |
75 |
79 |
79 |
75 |
99 |
149 |
160 |
160 |
149 |
198 |
299 |
320 |
320 |
-29℃ |
37 |
49 |
73 |
79 |
79 |
72 |
96 |
145 |
160 |
160 |
143 |
192 |
290 |
320 |
320 |
-40℃ |
35 |
47 |
70 |
79 |
79 |
70 |
94 |
142 |
160 |
160 |
140 |
189 |
283 |
320 |
320 |
VPL 15W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE |
|||||||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
||||||||||||||
temperature |
120V |
240V |
480V |
||||||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
26 |
35 |
53 |
66 |
66 |
53 |
70 |
107 |
131 |
131 |
107 |
140 |
213 |
262 |
262 |
-18℃ |
24 |
34 |
50 |
66 |
66 |
50 |
67 |
99 |
131 |
131 |
10 |
134 |
198 |
262 |
262 |
-29℃ |
24 |
32 |
49 |
66 |
66 |
49 |
66 |
98 |
130 |
131 |
98 |
131 |
195 |
259 |
262 |
-40℃ |
23 |
30 |
47 |
64 |
66 |
47 |
64 |
94 |
126 |
131 |
94 |
128 |
189 |
253 |
262 |
VPL 20W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE |
|||||||||||||||
Ambient |
Maximum circuit Length (in Meter) per circuit breaker |
||||||||||||||
temperature |
120V |
240V |
480V |
||||||||||||
at start-up |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
15A |
20A |
30A |
40A |
50A |
10℃ |
20 |
26 |
40 |
53 |
56 |
40 |
53 |
79 |
107 |
113 |
79 |
107 |
158 |
213 |
226 |
-18℃ |
18 |
26 |
38 |
50 |
56 |
38 |
50 |
76 |
101 |
113 |
76 |
101 |
152 |
201 |
226 |
-29℃ |
18 |
24 |
37 |
49 |
56 |
37 |
49 |
75 |
99 |
113 |
73 |
98 |
149 |
198 |
226 |
-40℃ |
18 |
24 |
37 |
49 |
56 |
35 |
47 |
73 |
98 |
113 |
70 |
94 |
146 |
195 |
226 |