Electrical Heating Cable Infomation

BTV Heating Cable for Freeze Protection (under 60℃ Max. Process Temperature)
1.Product Overview
TEMPERATURE RATING

Maximum maintain or continuous exposure temperature(power on)

65℃

Maximum intermittent exposure temperature, 1000 hours (power on or off)

85℃

Minimum installation temperature

-40℃



2. Nominal Power Output Rating on Metal Pipes @ 220V / 240V


3. Maximum Circuit Lengths based on Circuit Breaker Size

3 BTV-CR/CT

Ambient

Maximum circuit Length (in Meter) per circuit breaker

temperature

120V

240V

at start-up

15A

20A

30A

40A

15A

20A

30A

40A

10

101

101

101

101

201

201

201

201

-18

61

81

101

101

120

162

201

201

-29

53

72

101

101

107

142

201

201

-40

47

62

94

101

94

125

189

201

5 BTV-CR/CT

Ambient

Maximum circuit Length (in Meter) per circuit breaker

temperature

120V

240V

at start-up

15A

20A

30A

40A

15A

20A

30A

40A

10

70

82

82

82

140

165

165

165

-18

43

58

82

82

87

116

165

165

-29

38

50

76

82

76

101

152

165

-40

34

44

67

82

67

90

134

165

8 BTV-CR/CT

Ambient

Maximum circuit Length (in Meter) per circuit breaker

temperature

120V

240V

at start-up

15A

20A

30A

40A

15A

20A

30A

40A

10

46

61

64

64

91

122

128

128

-18

30

40

61

64

61

81

122

128

-29

26

35

53

64

53

72

107

128

-40

24

32

47

64

47

64

96

128

10 BTV-CR/CT

Ambient

Maximum circuit Length (in Meter) per circuit breaker

temperature

120V

240V

at start-up

15A

20A

30A

40A

15A

20A

30A

40A

10

37

49

55

55

73

96

110

110

-18

24

34

49

55

49

66

99

110

-29

21

29

43

55

44

58

87

110

-40

20

26

38

52

38

52

78

104





B. XTV Heating Cable for Freeze Protection (above 60℃ Max. Process Temperature)
1. Product Overview
TEMPERATURE RATING

Maximum maintain or continuous exposure temperature(power on)

121℃

Maximum intermittent exposure temperature, 1000 hours (power on or off)

215℃

Minimum installation temperature

-40℃





2. Nominal Power Output Rating on Metal Pipes @ 220V / 240V




3. Maximum Circuit Lengths based on Circuit Breaker Size

5 HXTV

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

10

         55

         73

       110

       117

       117

       110

       146

       219

       233

       233

-18

         49

         64

         98

       117

       117

         96

       128

       191

       233

       233

-29

         46

         61

         93

       117

       117

         90

       120

       181

       233

       233

-40

         44

         59

         88

       117

       117

         87

       116

       174

       232

       233

10 HXTV

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

10

         34

         44

         67

         82

         82

         67

         90

       134

       165

       165

-18

         29

         40

         59

         79

         82

         59

         79

       117

       157

       165

-29

         29

         38

         58

         76

         82

         56

         75

       113

       151

       165

-40

         27

         37

         55

         73

         82

         53

         72

       108

       143

       165

15 HXTV

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

10

         23

         30

         46

         61

         67

         46

         61

         91

       122

       136

-18

         20

         27

         41

         55

         67

         40

         53

         81

       108

       134

-29

         20

         26

         40

         52

         66

         38

         50

         76

       102

       128

-40

         18

         24

         38

         50

         62

         37

         49

         73

         98

       123

20 HXTV

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

10

         18

         24

         37

         49

         58

         35

         46

         70

         93

       116

-18

         15

         21

         32

         43

         55

         30

         41

         62

         84

       105

-29

         15

         20

         30

         41

         52

         30

         40

         61

         81

       101

-40

         15

         20

         30

         40

         50

         29

         38

         58

         78

         98





C. VPL Heating Cable(Power-Limiting) for Temperature Maintenance
1. Product Overview
TEMPERATURE RATING
Maximum exposure temperature (power off)

260℃

Minimum installation temperature

-40℃

Maximum Continuous maintain (power on) temperature table

CABLE

120V

208V

230V

240V

277V

480V

5VPL1-CT

230

10VPL1-CT

205

15VPL1-CT

170

20VPL1-CT

150

5VPL2-CT

235

230

230

225

10VPL2-CT

220

210

205

200

15VPL2-CT

210

190

170

115

20VPL2-CT

150

150

150

5VPL4-CT

230

10VPL4-CT

205

15VPL4-CT

170

20VPL4-CT

150



2. Nominal Power Output Rating on Metal Pipes @ 220V / 240V




C. VPL Heating Cable(Power-Limiting) for Temperature Maintenance

VPL 5W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

 480V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

 15A

 20A

 30A

 40A 

 50A

10

260

     79

   107

   113

   113

   113

   160

   209

   226

   226

   226

   320

   418

   451

   451

-18

240

     73

     99

   113

   113

   113

   148

   197

   226

   226

   226

   296

   393

   451

   451

-29

235

     72

     96

   113

   113

   113

   143

   191

   226

   226

   226

   287

   381

   451

   451

-40

225

     69

     93

   113

   113

   113

   139

   186

   226

   226

   226

   277

   372

   451

   451

VPL 10W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

 480V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

 15A

 20A

 30A

 40A 

 50A

10

     40

     53

     79

     79

     79

     79

   107

   160

   160

   160

   158

   213

   320

   320

   320

-18

     37

     50

     75

     79

     79

     75

     99

   149

   160

   160

   149

   198

   299

   320

   320

-29

     37

     49

     73

     79

     79

     72

     96

   145

   160

   160

   143

   192

   290

   320

   320

-40

     35

     47

     70

     79

     79

     70

     94

   142

   160

   160

   140

   189

   283

   320

   320

VPL 15W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

 480V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

 15A

 20A

 30A

 40A 

 50A

10

     26

     35

     53

     66

     66

     53

     70

   107

   131

   131

   107

   140

   213

   262

   262

-18

     24

     34

     50

     66

     66

     50

     67

     99

   131

   131

     10

   134

   198

   262

   262

-29

     24

     32

     49

     66

     66

     49

     66

     98

   130

   131

     98

   131

   195

   259

   262

-40

     23

     30

     47

     64

     66

     47

     64

     94

   126

   131

     94

   128

   189

   253

   262

VPL 20W - MAXIMUM CIRCUIT LENGTHS BASED ON CIRCUIT BREAKER SIZE

Ambient

Maximum circuit Length (in Meter) per circuit breaker

 temperature

120V

240V

 480V

at start-up

15A

20A

30A

40A

50A

15A

20A

30A

40A

50A

 15A

 20A

 30A

 40A 

 50A

10

     20

     26

     40

     53

     56

     40

     53

     79

   107

   113

     79

   107

   158

   213

   226

-18

     18

     26

     38

     50

     56

     38

     50

     76

   101

   113

     76

   101

   152

   201

   226

-29

     18

     24

     37

     49

     56

     37

     49

     75

     99

   113

     73

     98

   149

   198

   226

-40

     18

     24

     37

     49

     56

     35

     47

     73

     98

   113

     70

     94

   146

   195

   226